SUNTEC ENERGY SYSTEMS
Industrial Dual Bloc Burners

Industrial Dual Bloc Burners

Send Inquiry

 Industrial Dual Bloc Burners

We have established ourselves as a renowned suppliers of Industrial Dual Bloc Burners. These products are widely demanded for industrial processes and big civil installations as the burners offered by us require very low maintenance and deliver high performance. These burners are manufactured by our vendors using high quality components and materials. We examine all our products for flaws and errors to ensure optimal fluid-dynamics conditions and wide modulation ratio. We are able to offer these Industrial Dual Bloc Burners in many specifications to our valued clients.

Technical Data

Model

TI 10

TI 11

TI 12

TI 13

TI 14

Burner operation mode

Modulating




Modulation ratio at max. output

Natural gas

1 : 6

1 : 6

1 : 6

1 : 6

1 : 5

LPG

1 : 5

1 : 5

1 : 5

1 : 5

1 : 4

Light oil

1 : 4

1 : 4

1 : 4

1 : 4

1 : 3,5

Heavy oil

1 : 3

1 : 3

1 : 3

1 : 3

1 : 3

Servomotor

run time

type

SQM10

s

42









Heat output


Natural gas

kW

870/
3000 - 5200

1160/
4200 - 7000

1450/
6000 - 8700

1830/
7800 - 11000

2400/
8500 - 13000

Mcal/h

748/
2580
- 4472

998/
3612 - 6020

1247/
5160 - 7482

1574/
6708 - 9460

2064/
7310 - 11180


LPG

kW

1040/
3000
- 5200

1400/
4200 - 7000

1740/
6000 - 5700

2200/
7800 - 11000

3000/
8500 - 13000

Mcal/h

894/
2580- 4472

1204/
3612 - 6020

1496/
5160 - 7482

1892/
6708 - 9460

2580/
7310 - 11180


Light oil

kW

1300/
3000 - 5200

1750/
4200 - 7000

2170/
6000 - 8700

2750/
7800 - 11000

3400/
8500 - 13000

Mcal/h

1118/
2580 - 4472

1505/
3612 - 6020

1866/
5160 - 7482

2365/
6708 - 9460

2924/
7310 - 11180


Heavy oil

kW

1700/
3000 - 5200

2330/
4200 - 7000

2900/
6000 - 8700

3660/
7800 - 11000

4000/
8500 - 13000

Mcal/h

1462/
2580 - 4472

2004/
3612 - 6020

2494/
5160 - 7482

3148/
6708 - 9460

3440/
7310 - 11180

Working temperature

oC min./max.

-15/60

Fuel / Air Data



Light
oil

Net calorific value

kWh/kg

11,8

Kcal/kg

10200

Viscosity at 20oC

mm2/s (cSt)

4 - 6

Delivery

kg/h

111/253 - 438

148/354 - 590

183/506 - 734

232/658 - 927

287/717 - 1102

Fuel temperature

max.oC

50



Heavy
oil

Net calorific value

kWh/kg

11,1 - 11,3

Kcal/kg

9545 - 9720

Viscosity at 20oC

mm2/s (cSt)

500

Delivery

kg/h

152/268 - 464

208/375 - 625

259/536 - 777

326/696 - 982

357/759 - 1164

Fuel temperature

max.oC

140

Atomised pressure

bar

25 - 28


G20


Net calorific value

kWh/Nm3

10

Density

kg/Nm3

0,71

Gas delivery

Nm3/h

87/300 - 520

116/420 - 700

145/600 - 870

183/780 - 1100

240/850 - 1300


G25

Net calorific value

kWh/Nm3

8,6

Density

kg/Nm3

0,78

Gas delivery

Nm3/h

101/349 - 605

135/488 - 814

169/698 - 1012

213/907 - 1279

279/988 - 1512


LPG

Net calorific value

kWh/Nm3

25,8

Density

kg/Nm3

2,02

Gas delivery

Nm3/h

40/116- 202

54/163 - 271

67/233 - 337

85/302 - 426

116/329 - 504

Fan

type

Centrifugal with reverse curve blades

Air temperature

max oC

150

Electrical data

Electrical supply

Ph / Hz / V

1/50-60/230 - (1/50-60/110 on request)

Control box

type

LFL 1.333 - LFL 1.335 (Intermittent working) - LGK 16 (Continuos working)

Auxiliary electrical supply

kW

0,63

Total current

A

2,7 - 5,7

Protection level

IP

54

Ignition
transformer

V1 - V2

230 V - 1x8 KV

I1 - I2

1,4A - 30 mA

Operation

Intermittent (at least one stop every 24 h) - Continuos (at least one stop every 72 h)

Approval Emissions

Sound pressure

dB(A)

--

Sound power

W

--


Light
Oil

CO emission

mg/kWh

< 110

Grade of smoke indicator

No Bacharach

< 1

NOx emission

mg/kWh

< 250

Heavy
Oil

CO emission

mg/kWh

Depending on the fuel amount

Grade of smoke indicator

No Bacharach

Depending on the fuel amount

NOx emission

mg/kWh

Depending on the fuel amount

G20

CO emission

mg/kWh

< 100

NOx emission

mg/kWh

< 170

Directive

89/336 - 73/23 - 98/37 - 90/396 CEE

Conforming to

EN 267 - EN 676

Certification

--


Reference conditions:
  • Temperature: 20oC - Pressure: 1013,5 mbar - Altitude: 100 m a.s.l.
  • Noise measured at a distance of 1 meter.
Product Specification

OIL BURNER
Combustion head:
  • Forced draught oil burner with two stage progressive or modulating operation, with separate supplies, fully automatic, made up of:
  • Sheet-steel airlock painted with a cover for access to the internal elements
  • Air damper for air setting with variable profile cam controlled by a servomotor
  • Mobile combustion head (except for TI 14 model), that can be set on the basis of required output, fitted with:
    • stainless steel end cone, resistant to corrosion and high temperatures
    • ignition electrodes
    • pilot burner (TI13 - TI14 models) with gas train
    • flame stability disk
  • Photocell for flame detection
  • Minimum air pressure switch
  • Nozzle pipe
  • Safety nozzle valve
  • Valves group with safety oil valves
  • Automatic regulator of oil capacity controlled by a servomotor
  • Maximum oil pressure switch on the return circuit
  • Pressure gauge on the delivery circuit
  • Pressure gauge on the return circuit
  • Flame inspection window
  • Shunt box with ignition transformer
  • IP 54 electric protection level.
Conforming to:
  • 89/336/EEC directive (electromagnetic compatibility)
  • 73/23/EEC directive (low voltage)
  • 98/37/EEC directive (machinery)
  • EN 267 (liquid fuel burners).
Standard equipment:
  • Screws for fixing the burner flange to the boiler
  • Thermal screen
  • Instruction handbook for installation, use and maintenance
  • Spare parts catalogue.
Available accessories to be ordered separately:
  • Flexible tubes
  • Return nozzles
  • High pressure oil filter
  • Circulation group (by-pass valve)
  • Check valve
  • Potentiometer kit for the servomotor.